Parameterizing and Configuring
Parameters
116
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Parameter name Value Meaning Description
dec. Hex.
2 0x02 read in Synchronization of parameter data activated. The
data in the connected IO-Link device serve as refer-
ence data.
3 0x03 Deactivated, clear
Synchronization of parameter data deactivated. The
data set in the master is deleted.
Activate Quick
Start-Up
For fast applications (e.g. tool changing applications) the start-up time of IO-Link devices can
be shortened. The start-up time defined in the IO-Link specification (TSD = Device Detection
Time) is reduced.
0 0x00 No
The start-up time is within the specified range (0.5 s).
All IO-Link devices in accordance with the specifica-
tion can be operated.
1 0x01 Yes The start-up time is reduced to approx. 100 ms. It is
not supported by every IO-Link device. It can thus be
necessary to check if the used IO-Link device starts in
this mode.
Device parameter-
ization via GSD
(GSD)
0 0x00 inactive
The port is generic or is not parameterized.
1 0x01 Active In PROFINET the port is parameterized with a specific
device type from the GSDML-file.
Cycle time
0 0x00 Automatic
The lowest cycle time supported by the device is
taken from the table.
1…
191
0x01
0xBF
0.8 = 132,8 ms Settable in steps of 0.8 or 1.6 ms.
255 0xFF Automatic, compatible Compatibility mode The mode solves possible com-
munication problems with sensors of the SGB family
from IFM.
Revision
0 0x00 Automatic
The Master defines the IO-Link revision automatically.
1 0x01 V1.0 IO-Link Revision V 1.0 is used.
Process input data
invalid (PDIN in-
valid)
0 0x00 Diagnostic generated
If the process data are invalid, a respective diagnostic
message is generated.
1 0x01 No diagnostic generated Invalid process data do not cause a diagnostic mes-
sage.
Deactivate dia-
gnostics
Influences the sending of IO-Link-Events from the master to the fieldbus. Depending on the
parameterization, the master transmits Events based on their priority to the fieldbus or not.
0 0x00 No The master transmits all IO-Link Events to the field-
bus.
1 0x01 Notifications The master transmits all IO-Link Events to the fieldbus
except for IO-Link notifications.
2 0x02 Notifications and warn-
ings
The master transmits all IO-Link Events to the fieldbus
except for IO-Link notifications and warnings.
3 0x03 Yes The master doesn't transmit any IO-Link Event to the
fieldbus.
Process inpput
data mapping
(Mapping PDIN)
Optimization of the process data mapping for the used fieldbus: The I/O-Link-data can be
swapped depending on the used fieldbus in order to achieve an optimized data mapping on
the fieldbus side.
PROFINET:
With PROFINET, the parameter is permanently set to 0x00 = direct and cannot be changed.