Byte no. Bit no. Description
7 6 5 4 3 2 1 0
3 Port IO-Link port which sends an event
4 Event Code high byte High or- low byte of the error code sent
5 Event Code low byte
… …
223 Qualifier see byte 2 - 5
224 Port
225 Event Code high byte
226 Event Code low byte
Subindex 66: Set Default Parameterization
Writing this object sets the IO-Link master back to factory settings. Any parameter setting and
configuration is overwritten. The data storage buffer is deleted as well.
Entity_Port IO-Link sub index Read/write Length
0 66 Write 4 byte
Structure of the reset command:
Byte 3 Byte 2 Byte 1 Byte 0
0xEF 0xBE 0xAD 0xDE
Subindex 67: Teach Mode
The master reads all data (device-Id, vendor-ID, serial number, etc.) from the connected device
and saves them. All all previously saved device data are overwritten.
Entity_Port IO-Link sub index Read/write Length
0 67 Write 1 byte
Structure of the Teach command:
Byte 0
0x00 Teach all ports
0x01 Teach port 1
0x02 Teach port 2
0x03 Teach port 3
0x04 Teach port 4
0x05 Teach port 5
0x06 Teach port 6
0x07 Teach port 7
0x08 Teach port 8
0x09…0xFF reserved