V02.00 | 2019/10
81
Instance 124 – 8 byte IN/8 byte OUT, diagnostics
The description of the input data can be found in chapter “Operating” [}126]
Word
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status word
0x00 - FCE - - - - V1 - V2 - - - - - - Diag
Inputs
0x01 - DI14
(SIO)
- DI12
(SIO)
- DI10
(SIO)
- DI8
(SIO)
DXP7 DI6
(SIO)
DXP5 DI4
(SIO)
DXP3 DI2
(SIO)
DXP1 DI0
(SIO)
Process input data valid
0x02 - DVS
14
- DVS
12
- DVS
10
- DVS8 - DVS6 - DVS4 - DVS2 - DVS0
IO-Link process input data
0x03…
0x06
4 words per port
…
0x1F…
0x22
Diagnostics
VAUX1/VAUX2
0x23 VERR
V2 C7
ch15
VERR
V2 C6
ch13
VERR
V2 C5
ch11
VERR
V2 C4
ch9
- - - - VERR
V1 C7
ch14
VERR
V1 C6
ch12
VERR
V1 C5
ch10
VERR
V1 C4
ch08
VERR
V1 C3
ch6/7
VERR
V1 C2
ch4/5
VERR
V1 C1
ch2/3
VERR
V1 C0
ch0/1
DXP channels
0x24 - - - - - - - - ERR
DXP 7
- ERR
DXP 5
- ERR
DXP 3
- ERR
DXP 1
-
IO-Link port diagnostics
Port 1
0x25 GEN
ERR
OVL V
HIGH
V
LOW
ULVE LLVU O
TMP
PRM
ERR
EVT1 EVT2 PD
INV
HW
ERR
DS
ERR
CFG
ERR
PPR -
…
Port 8
0x2C GEN
ERR
OVL V
HIGH
V
LOW
ULVE LLVU O
TMP
PRM
ERR
EVT1 EVT2 PD
INV
HW
ERR
DS
ERR
CFG
ERR
PPR -