Commissioning
Commissioning the device in EtherNet/IP™
82
Hans Turck GmbH & Co. KG | T +49 208 4952-0 | F +49 208 4952-264 | more@turck.com | www.turck.com
Instance 125 – 8 byte IN/8 byte OUT
The description of the input data can be found in chapter “Operating” [}126]
Word
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Status word
0x00 - FCE - - - - V1 - V2 - - - - - - Diag
Inputs
0x01 - DI14
(SIO)
- DI12
(SIO)
- DI10
(SIO)
- DI8
(SIO)
DXP7 DI6
(SIO)
DXP5 DI4
(SIO)
DXP3 DI2
(SIO)
DXP1 DI0
(SIO)
Process input data valid
0x02 - DVS
14
- DVS
12
- DVS
10
- DVS8 - DVS6 - DVS4 - DVS2 - DVS0
IO-Link process input data
0x03…
0x06
4 words per port
…
0x1F…
0x22
Output assembly instances
EtherNet/IP™
Connection
Output Assembly Control word
[byte]
DXP outputs
[byte]
IO-Link out-
puts [byte]
VAUX [byte]
Instance Size [8 bit]
Exclusive
Owner
104 262 2 2 256 2
IOL 4 IN/4
OUT
150 38 2 2 32 2
IOL 6 IN/6
OUT
151 54 2 2 48 2
IOL 8 IN/8
OUT
152 70 2 2 64 2
Instance 104 – Exclusive Owner
The description of the output data can be found in chapter “Operating” [}128]
Word
no.
Bit no.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Control Word
0x00 - reserved
DXP outputs
0x01 - - - - - - - - DXP7 - DXP5 - DXP3 - DXP1 -
IO-Link process output data
0x02…
0x11
16 words per port
…
0x72…
0x81