02 he ating/Cooling Changeover
This menu is not visible if the thermostat is registered
to a controller. Heating/cooling changeover will be
controlled by a physical heating/cooling switch (Base
or Base PRO) or the interface (Base PRO only), if
connected.
03 eCo mo de set BaCK temPerature
In this menu the setback temperature for whenever the
channel is in ECO mode is set.
The setting adjusts the current setpoint with the set
value. In heating mode the setpoint is reduced, and in
cooling mode it is increased.
If the setback temperature is set to 0, the thermostat
will remain unaffected if a program sets the system in
ECO mode.
This menu is not visible if an interface is connected to
the system. The setting is then available in an interface
(Base PRO only).
To change this setting:
1. Press OK to enter parameter edit mode.
2. Use buttons - or + (T-149 = or ) to change the
parameter.
Default: 4 ˚C
Setting range: 0 – 11 ˚C, 0.5 ˚C increments
3. Press OK to confirm change and to return to the
settings menu.
04 Co ntrol mode
In this menu control mode for the thermostat is set.
If an external sensor is connected to the thermostat, a
control mode must be chosen to accommodate the extra
functionality of the sensor.
Current control mode is displayed (RT, RFT, RS or RO).
To change this setting:
1. Press OK to enter parameter edit mode.
2. Use buttons - or + (T-149 = or ) to change
control mode (see list below).
T-149
T-146/
T-148 Description
RT Room temperature
RFT Room temperature with external
floor sensor
RS Remote sensor
RO Room temperature with remote
outdoor sensor
3. Press OK to confirm the change and return to the
settings menu.
05 hi gh floor temPerature limitation
In this menu a limit on the maximum allowable floor
temperature is set.
This menu is only visible if control mode RFT is activated
in settings menu 04. For systems with an interface this
menu only shows the set value, changes are done in the
interface (Base PRO only).
To change this setting:
1. Press OK to enter parameter edit mode.
2. Use buttons - or + (T-149 = or ) to change the
parameter.
Default: 26 ˚C
Setting range: 2035 ˚C, 0.5 ˚C increments
NOTE!
This parameter cannot be set lower than the
set value in settings menu 06 Low floor
temperature limitation.
3. Press OK to confirm the change and return to the
settings menu.
UK
CZ
DE
DK
EE
ES
FI
FR
HR
HU
IT
LT
LV
NL
NO
PL
PT
RO
RU
SE
SK
86
UPONOR SMATRIX BASE/BASE PRO · INSTALLATION AND OPERATION MANUAL

Table of Contents

Other manuals for Uponor Smatrix Base

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Uponor Smatrix Base and is the answer not in the manual?

Uponor Smatrix Base Specifications

General IconGeneral
BrandUponor
ModelSmatrix Base
CategoryHeating System
LanguageEnglish

Related product manuals