30
DS2 Function Dip Switches
ON - Down on right
OFF - Down on left
Switch Setting Factory Settings are shown in bold type
1
Solenoid Lock Enable /
Gate in Operation Indicator
ON Solenoid lock output energizes half second
before gate begins to move and releases 3
seconds after the gate begins to move. For gate
in operation indicator to operate DS1 SW 5 must
also be ON. (Energizes = +12 vdc output 1.5 amp
max)
OFF Solenoid lock / gate in operation indicator is
inactive
2
Magnetic Lock Enable ON Magnetic lock output energizes on Master Limit
and releases half second before gate begins to
open. (Energizes = +12 vdc output 1.5 amp max)
OFF Magnetic lock output is inactive
3
Security Shunt Circuit Enable /
Open Gate Indicator
ON Security shunt circuit relay is active (closed
circuit)(wire in parallel) Relay activates half
second before gate begins to open and stays
activated until 4 seconds after gate reaches a
closed limit
OFF Security shunt circuit relay is inactive (open
circuit)
4
Motion Detector Enable ON Enables motion detector input J2 pin 12 (if input
is activated, gate will not open)
OFF Disables motion detector input J2 pin 12
DS2 Switches