Table 70: Temperature input fault 1 settings
Index Parameter Min Max Unit Default ID Description
P3.9.6.1
Temperature Signal
1
0 63 0 739
B0 = Temperature Sig-
nal 1
B1 = Temperature Sig-
nal 2
B2 = Temperature Sig-
nal 3
B3 = Temperature Sig-
nal 4
B4 = Temperature Sig-
nal 5
B5 = Temperature Sig-
nal 6
P3.9.6.2
Alarm Limit 1 -30.0 200.0 °C 130.0 741
P3.9.6.3 Fault Limit 1 -30.0 200.0 °C 155.0 742
P3.9.6.4
Fault Limit Response
1
0 3 2 740
0 = No response
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
NOTE!
Temperature input settings are only available if a B8 or BH option board is
installed.
PARAMETERS MENU VACON · 133