Table 71: Temperature input fault 2 settings
Index Parameter Min Max Unit Default ID Description
P3.9.6.5
Temperature Signal
2
0 63 0 763
B0 = Temperature Sig-
nal 1
B1 = Temperature Sig-
nal 2
B2 = Temperature Sig-
nal 3
B3 = Temperature Sig-
nal 4
B4 = Temperature Sig-
nal 5
B5 = Temperature Sig-
nal 6
P3.9.6.6
Alarm Limit 2 -30.0 200.0 °C 130.0 764
P3.9.6.7 Fault Limit 2 -30.0 200.0 °C 155.0 765
P3.9.6.8
Fault Limit Response
2
0 3 2 766
0 = No response
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
NOTE!
Temperature input settings are only available if a B8 or BH option board is
installed.
VACON · 134 PARAMETERS MENU