Table 72: AI low protection settings
Index Parameter Min Max Unit Default ID Description
P3.9.8.1
Analogue Input Low
Protection
0 2 767
0 = No protection
1 = Protection enabled
in Run state
2 = Protection enabled
in Run and Stop state
P3.9.8.2
Analogue Input Low
Fault
0 5 0 700
0 = No action
1 = Alarm
2 = Alarm + preset
fault frequency
(P3.9.1.13)
3 = Alarm + previous
frequency reference
4 = Fault (Stop accord-
ing to stop mode)
5 = Fault (Stop by
coasting)
Table 73: User Defined Fault 1
Index Parameter Min Max Unit Default ID Description
P3.9.9.1 User Defined Fault 1 N/A N/A
DigIN
Slot0.1
15523
OPEN = No operation
CLOSED = Fault activa-
ted
P3.9.9.2
Response to User
Defined Fault 1
N/A N/A
Fault,Coa
st
15525
Table 74: User Defined Fault 2
Index Parameter Min Max Unit Default ID Description
P3.9.10.1 User Defined Fault 2 N/A N/A
DigIN
Slot0.1
15524
OPEN = No operation
CLOSED = Fault activa-
ted
P3.9.10.2
Response to User
Defined Fault 2
N/A N/A
Fault,Coa
st
15526