Table 91: Pressure loss compensation parameters
Index Parameter Min Max Unit Default ID Description
P3.13.7.1 Enable Setpoint 1 0 1 0 1189
0 = Disabled
1 = Enabled
P3.13.7.2
Setpoint 1 Max Com-
pensation
Varies Varies Varies Varies 1190
P3.13.7.3 Enable Setpoint 2 0 1 0 1191 See P3.13.7.1.
P3.13.7.4
Setpoint 2 Max Com-
pensation
Varies Varies Varies Varies 1192
See P3.13.7.2.
Table 92: Soft fill settings
Index Parameter Min Max Unit Default ID Description
P3.13.8.1 Enable Soft Fill 0 1 0 1094
0 = Disabled
1 = Enabled
P3.13.8.2 Soft Fill Frequency 0.00 50.00 Hz 20.00 1055
P3.13.8.3 Soft Fill Level Varies Varies Varies 0.0000 1095
P3.13.8.4 Soft Fill Timeout 0 30000 s 0 1096
0 = No timeout
P3.13.8.5
PID Soft Fill Timeout
Response
0 3 2 748
0 = No action
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
PARAMETERS MENU VACON · 147