P3.3.3.9 PRESET FREQUENCY 7 (ID 130)
Use this parameter to set the preset frequency reference when the preset frequencies
function is used.
Select the preset frequencies with the digital input signals.
VALUE 0 SELECTED FOR PARAMETER P3.3.3.1:
To set Preset Frequency 0 as reference, set the value 0 Preset Frequency 0 for P3.3.1.5 (I/O
Control Reference A Selection).
To make a selection of a preset frequency between 1 and 7, give digital inputs to P3.3.3.10
(Preset Frequency Selection 0), P3.3.3.11 (Preset Frequency Selection 1), and/or P3.3.3.12
(Preset Frequency Selection 2). The different sets of active digital inputs determine the
preset frequency. You can find more data in the table below. The values of the preset
frequencies stay automatically between the minimum and maximum frequencies (P3.3.1.1
and P3.3.1.2).
Necessary step
Activated frequency
Make a selection of the value 0 for parameter P3.3.1.5. Preset frequency 0
Table 123: The selection of preset frequencies when P3.3.3.1 = Binary coded
Activated digital input signal Activated frequency
reference
Preset Freq Sel2
(P3.3.3.12)
Preset Freq Sel1
(P3.3.3.11)
Preset Freq Sel0
(P3.3.3.10)
Preset frequency 0
Only if Preset Freq 0 is set
as frequency reference
source with P3.3.3.1.5,
P3.3.1.6, P3.3.1.7 or
P3.3.1.10.
* Preset frequency 1
* Preset frequency 2
* * Preset frequency 3
* Preset frequency 4
* * Preset frequency 5
* * Preset frequency 6
* * * Preset frequency 7