Table 12: M1 Quick Setup
Index Parameter Min Max Unit Default ID Description
1.14 Energy Optimization 0 1 0 666
0 = Disabled
1 = Enabled
1.15 Identification 0 2 0 631
0 = No action
1 = At standstill
2 = With rotation
1.16 Start Function 0 1 0 505
0 = Ramping
1 = Flying Start
1.17 Stop Function 0 1 0 506
0 = Coasting
1 = Ramping
1.18 Automatic Reset 0 1 0 731
0 = Disabled
1 = Enabled
1.19
Response to External
Fault
0 3 2 701
0 = No action
1 = Alarm
2 = Fault (Stop accord-
ing to stop mode)
3 = Fault (Stop by
coasting)
1.20
Response to AI Low
Fault
0 5 0 700
0 = No action
1 = Alarm
2 = Alarm+preset fault
frequency (P3.9.1.13)
3 = Alarm + previous
frequency
4 = Fault (Stop accord-
ing to stop mode)
5 = Fault (Stop by
coasting)
1.21
Remote Control
Place
0 1 0 172
0 = I/O control
1 = Fieldbus control
QUICK STARTUP GUIDE VACON · 37