Table 12: M1 Quick Setup
Index Parameter Min Max Unit Default ID Description
1.22
I/O Control Refer-
ence A Selection
0 9 6 117
0 = Preset Frequency 0
1 = Keypad Reference
2 = Fieldbus
3 = AI1
4 = AI2
5 = AI1+AI2
6 = PID Reference
7 = Motor Potentiome-
ter
8 = Joystick Reference
9 = Jogging Reference
10 = Block Out.1
11 = Block Out.2
12 = Block Out.3
13 = Block Out.4
14 = Block Out.5
15 = Block Out.6
16 = Block Out.7
17 = Block Out.8
18 = Block Out.9
19 = Block Out.10
The application that
you set with parameter
1.2 gives the default
value.
1.23
Keypad Control Ref-
erence Selection
0 9 1 121
See P1.22.
1.24
Fieldbus Control
Reference Selection
0 9 2 122
See P1.22.
1.25 AI1 Signal Range 0 1 0 379
0= 0..10V / 0..20mA
1= 2..10V / 4..20mA
1.26 AI2 Signal Range 0 1 1 390
0= 0..10V / 0..20mA
1= 2..10V / 4..20mA
1.27 RO1 Function 0 61 2 11001 See P3.5.3.2.1
1.28 RO2 Function 0 56 3 11004 See P3.5.3.2.1
1.29 RO3 Function 0 56 1 11007 See P3.5.3.2.1
1.30 AO1 Function 0 31 2 10050 See P3.5.4.1.1