Parameters vacon • 103
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
P3.5.1.16 Run Interlock 1 DigIN Slot0.2 1041
Drive may be ready but start is blocked as long as
interlock is on (Damper interlock).
P3.5.1.17 Run Interlock 2 DigIN Slot0.2 1042 As above.
P3.5.1.21 Preset Freq Sel0 DigIN SlotA.4 419 Binary selector for Preset speeds (0-7). See page 99.
P3.5.1.22 Preset Freq Sel1 DigIN SlotA.5 420 Binary selector for Preset speeds (0-7). See page 99.
P3.5.1.23 Preset Freq Sel2 DigIN Slot0.1 421 Binary selector for Preset speeds (0-7). See page 99.
P3.5.1.24 MotPot UP DigIN Slot0.1 418
FALSE = Not active
TRUE = Active (Motor potentiometer reference
INCREASES until the contact is opened)
P3.5.1.25 MotPot DOWN DigIN Slot0.1 417
FALSE = Not active
TRUE = Active (Motor potentiometer reference
DECREASES until the contact is opened)
P3.5.1.27 Timer 1 DigIN Slot0.1 447
Rising edge starts Timer 1 programmed in Group 3.12:
Timer functions parameter group
P3.5.1.28 Timer 2 DigIN Slot0.1 448 See above
P3.5.1.29 Timer 3 DigIN Slot0.1 449 See above
P3.5.1.30 PID SP Boost DigIN Slot0.1 1046
FALSE = No boost
TRUE = Boost
P3.5.1.31 PID SP Selection DigIN Slot0.1 1047
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.32 ExtPID StartSignal DigIN Slot0.2 1049
FALSE = PID2 in stop mode
TRUE = PID2 regulating
This parameter will have no effect if the external PID-
controller is not enabled in Group 3.14: ExtPID Con-
troller.
P3.5.1.33 ExtPID SP Select DigIN Slot0.1 1048
FALSE = Setpoint 1
TRUE = Setpoint 2
P3.5.1.40 MainCounter1Reset DigIN Slot0.1 490
Reset the counter from digital input.
TRUE = Reset
P3.5.1.48 AutoClean Activ. DigIN Slot0.1 1715
Start the Auto-cleaning sequence.
The sequence will be aborted if activation signal is
removed before the sequence has been completed.
NOTE! The drive will start if the input is activated!
P3.5.1.49 Param. Set 1/2 Sel. DigIN Slot0.1 496
Parameter set 1/2 selection.
Open= Parameter Set 1
Closed= Parameter Set 2
P3.5.1.50 User Defined Fault 1 DigIN Slot0.1
1552
3
Digital input selection for activating User Defined Fault
(1 or 2).
Open= No operation
Closed= Fault Activated
P3.5.1.51 User Defined Fault 2 DigIN Slot0.1
1552
4
Digital input selection for activating User Defined Fault
(1 or 2).
Open= No operation
Closed= Fault Activated
P3.5.1.52 Energy Counter reset DigIN Slot0.1 1933 Energy Counter reset
P3.5.1.53 Mains supply on DigIN Slot0.1 1934 Mains supply on
P3.5.1.54 Flowmeter pulse DigIN Slot0.1 1953 Digital input for pulse flow meter (P3.23.1 = 1)
P3.5.1.55 Volume counters reset DigIN Slot0.1 1957 Digital input for Volume counters reset
P3.5.1.56 Minimum water level DigIN Slot0.2 1963 Digital input for minimum water level in the well
Table 73. Digital input settings