7.1.10.6 Group 3.9.6: Temperature input fault 2
NOTE! This parameter group is visible only with an option board for temperature measurement
(OPT-BH) installed.
Table 91. Temperature input fault 2 settings
Code Parameter Min Max Unit Default ID Description
P3.9.6.5 Temperature signal 2 0 63 0 763
Selection of signals to use for
alarm and fault triggering. B0 =
Temperature Signal 1
B1 = Temperature Signal 2
B2 = Temperature Signal 3
B3 = Temperature Signal 4
B4 = Temperature Signal 5
B5 = Temperature Signal 6
Max value is taken of the chosen
signals and used for alarm/fault
triggering.
NOTE! Only 6 first temperature
inputs are supported (counting
boards from slot A to slot E).
P3.9.6.6 Alarm limit 2 -30.0 200.0 °C 120.0 764
Temperature limit for trigging
alarm.
NOTE! Only inputs cho-
sen with parameter P3.9.6.5 are
compared.
P3.9.6.7 Fault limit 2 -30.0 200.0 °C 120.0 765
Temperature limit for trigging
alarm.
NOTE! Only inputs cho-
sen with parameter P3.9.6.5 are
compared.
P3.9.6.8 Fault limit response 2 0 3 2 766
0 = No response
1 = Alarm
2 = Fault (Stop according to stop
mode)
3 = Fault (Stop by coasting)