Parameters vacon • 121
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
Interval 2:
P3.12.2.1:
ON Time: 09:00:00
P3.12.2.2:
OFF Time: 13:00:00
P3.12.2.3:
Days: Saturday,
Sunday
P3.12.2.4: AssignToChannel: Time channel 1
Timer 1
The manual bypassing can be handled by a digital input 1 on slot A (by a different switch or connec-
tion to lighting).
P3.12.6.1:
Duration: 1800s (30 min)
P3.12.6.3:
Assign to channel: Time channel 1
P3.12.6.2:
Timer 1: DigIn SlotA.1 (Parameter located in digital inputs menu.)
Finally select the Channel 1 for the I/O Run command.
P3.5.1.1:
Control signal 1 A: Time Channel 1
Figure 36. Final configuration where Time channel 1 is used as control signal for start command
instead of a digital input.
OK OK OK
Interval 1 Days Days
Monday
Sunday
Tuesday
Wednesday
Thursday
Friday
ON Time
Days
Edit
Help
Add to favorites
STOP READY I/O STOP READY I/O STOP READY I/O
ID:1466 M3.12.1.3
07:00:00
17:00:00
0
ID: M3.12.1.3 ID: M3.12.1.3.1
OFF Time
9158.emf