Table 11. AC drive (380…480/500 V 3AC 50/60Hz, up to 800 V DC) DC-link input ratings
Enclosure
size
AC drive
type
DC supply
[V DC]
Max.
Recommended
PV Array Power
[kW]
V
max
PVa
(absolute
maximum)
[V DC]
PV input
operating
voltage range
[V DC]
Maximum
operating PV
input current
[A DC]
MM4
0003
300/436*-800
No tolerance
permissible,
0%
2.2 800 300/436*-800 4.0
0004 3.0 800 300/436*-800 5.0
0005 4.4 800 300/436*-800 6.0
0008 6.0 800 300/436*-800 9.0
0009 8.0 800 300/436*-800 11.0
0012 11.0 800 300/436*-800 13.0
MM5
0016 15.0 800 300/436*-800 18.0
0023 22.0 800 300/436*-800 26.0
0031 30.0 800 300/436*-800 34.0
MM6
0038 37.0 800 300/436*-800 42.0
0046 44.0 800 300/436*-800 51.0
0061 60.0 800 300/436*-800 68.0
0072 74.0 800 300/436*-800 80.0