Installation vacon • 21
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
* The minimum value is 300 V when the application version is AMIT1181_V205 and the drive is manufactured after
June 2019.
MR5
0016
436-800
No tolerance
permissible,
0%
15.0 800 436-800 18.0
0023 22.0 800 436-800 26.0
0031 30.0 800 436-800 35.0
MR6
0038 37.0 800 436-800 43.0
0046 44.0 800 436-800 52.0
0061 60.0 800 436-800 69.0
MR7
0072 74.0 800 436-800 82.0
0087 90.0 800 436-800 100.0
0105 110.0 800 436-800 121.0
MR8
0140 150.0 800 436-800 161.0
0170 180.0 800 436-800 198.0
0205 220.0 800 436-800 239.0
MR9A
0261 264.0 800 436-800 304.0
0310 320.0 800 436-800 361.0
MR9B 0386 400.0 800 436-800 454.0
MR10
0460 500.0 800 436-800 542.0
0520 500.0 800 436-800 613.0
0590 630.0 800 436-800 695.0
MR11
0651 710.0 800 436-800 766.0
0731 800.0 800 436-800 860.0
MR12
0820 900.0 800 436-800 966.0
0920 1000.0 800 436-800 1084.0
1040 1120.0 800 436-800 1225.0
1180 1260.0 800 436-800 1390.0
Table 11. AC drive (380…480/500 V 3AC 50/60Hz, up to 800 V DC) DC-link input ratings
Enclosure
size
AC drive
type
DC supply
[V DC]
Max.
Recommended
PV Array Power
[kW]
V
max
PVa
(absolute
maximum)
[V DC]
PV input
operating
voltage range
[V DC]
Maximum
operating PV
input current
[A DC]