Table 63. I/f start parameters
7.1.2.6
Group 3.1.4.13: Stabilators
Code Parameter Min Max Unit Default ID Description
P3.1.4.12.1 I/f start 0 1 0 534
0 = Disabled
1 = Enabled
P3.1.4.12.2 I/f start frequency 0.0 P3.1.1.2 % 15.0 535
Output frequency limit below
which the defined I/f start cur-
rent is fed to motor.
P3.1.4.12.3 I/f start current 0.0 100.0 % 80.0 536
The current fed to the motor
when the I/f start function is acti-
vated.
Code Parameter Min Max Unit Default ID Description
P3.1.4.13.1 TorqStabGain 0.0 500.0 % 50.0 1412
Gain of the torque stabilator in
open loop motor control opera-
tion.
P3.1.4.13.2 TorqStabGainFWP 0.0 500.0 % 50.0 1414
Gain of the torque stabilator at
field weakening point in open
loop motor control operation.
P3.1.4.13.3 TorqStabDampTC 0.0005 1.0000 s 0.0050 1413
Damping time of torque stabi-
lizer
P3.1.4.13.4
TorqStabDampTC
PMM
0.0005 1.0000 s 0.0500 1735
Damping time constant of torque
stabilizer for PM-motor.