120
•
vacon parameter descriptions
9
9.6 Analogue inputs (Control panel: Menu PAR -> P6)
6.4 AI1
FILTER
TIME
6.8 AI2
FILTER
TIME
This parameter, given a value greater than 0, activates the function that filters
out disturbances from the incoming analogue signal.
Long filtering time makes the regulation response slower. See
%
100%
63%
Par. 6.4
Par. 6.8
t[s]
Filtered signal
Unfiltered signal
Figure 9.14.
Figure 9.14: AI1 and AI2 signal filtering
6.2 AI1 C
USTOM
MINIMUM
6.3 AI1 C
USTOM
MAXIMUM
6.6 AI2 C
USTOM
MINIMUM
6.7 AI2 C
USTOM
MAXIMUM
These parameters set the analogue input signal for any input signal span from
minimum to maximum.