vacon parameters
8
8.1 Quick setup parameters (Virtual menu, shows when par. 17.2 = 1)
Code Parameter Min Max Unit Default ID Note
Motor nominal
voltage
180 690 V Varies 110
Check rating plate on the
motor.
Motor nominal
frequency
30,00 320,00 Hz
50,00 /
60,00
111
Check rating plate on the
motor.
Motor nominal
speed
30 20000 rpm
1440 /
1720
112
Default applies for a 4-
pole motor.
Motor nominal
current
0,2 x
I
Nunit
2,0 x
I
Nunit
A
I
Nunit
113
Check rating plate on the
motor.
Motor cos
(Power Factor)
0,30 1,00 0,85 120
Check rating plate on the
motor.
Current limit
0,2 x
I
Nunit
2,0 x
I
Nunit
A
1,5 x
I
Nunit
107 Maximum motor current
Torque boost 0 1 0 109
0 = Not used
1 = Used
P2.1
Remote control
place 1 selection
0 2 0 172
0 = I / O terminal
1 = Fieldbus
2 = Keypad
Start function
0
1 0 505
0 = Ramp
1 = Flying start
Stop function
0
1 0 506
0 = Coasting
1 = Ramp
Min frequency 0,00 P3.2 Hz 0,00 101 Minimum freq reference
Max frequency P3.1 320,00 Hz
50,00 /
60,00
102
Maximum freq refer-
ence
P3.3
Remote Control
Place 1 frequency
reference seclec-
tion
1 Varies 7 117
1 = Preset speed 0
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = PID
7 = AI1+ AI2
8 = Motor potentiometer
9 = Pulse train / Encoder
10 = AIE1
11 = Temperature input 1
12 = Temperature input 2
13 = Temperature input 3
Table 8.1: Quick setup parameters