EasyManua.ls Logo

Vacon 20 - 9.13 Automatic reset

Vacon 20
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
parameter descriptions vacon
133
9
9.13 Automatic reset (Control panel: Menu PAR -> P14)
14.1 A
UTOMATIC
RESET
Activate the Automatic reset after fault with this parameter.
NOTE: Automatic reset is allowed for certain faults only.
Fault: 1. Under v
oltage
2. Over voltage
3. Over current
4. Motor over temperature
5. Under load
14.3 T
RIAL
TIME
The Automatic restart function restarts the frequency converter when the
faults have disappeared and the waiting time has elapsed.
The time count starts from the first auto reset. If the number of faults occur-
ring during the trial time exceeds trail number (the value of P14.4), the fault
state becomes
active. Otherwise the fault is cleared after the trial time has
elapsed and the next fault starts the trial time count again. See Figure 9.22.
If a single fault remains during the trial time, a fault state is true.
Fault trigger
Motor stop signal
Mot or
start signal
Supervision
Restart 1 Restart 2
Trial time
par.14.3
Fault active
RESET/
Fault reset
Autor
e
set function: (Trials = 2)
Wait time
pa r.14.2
Wait t ime
pa r.14.2
Wait t ime
pa r.1 4. 2
Figure 9.22: Example of Automatic restarts with two restarts

Table of Contents

Other manuals for Vacon 20

Related product manuals