EasyManua.ls Logo

Vacon 20 - 6.2 Control I; O

Vacon 20
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
vacon 20 api vacon
55
6
6.2 Control I / O
Terminal Signal Factory preset Description
1 +10 Vref Ref. voltage out
Maximum load 10 mA
2 AI1 Analog signal in 1
Freq. reference
P)
0 - 10 V, Ri = 250 k
3GND
I / O signal ground
6 24 Vout 24 V output for DI's
±20%, max. load 50 mA
7DI_C
Digital Input
Common
Digital Input Common for DI1-
DI6, refer to Table 6.3 for DI
sink type
8 DI1 Digital input 1
Start forward
P)
Positive, Logic1: 18…+30V,
Logic0: 0…5V;
Negative, Logic1: 0…10V,
Logic0: 18…30V;
Ri = 10K (floating)
9 DI2 Digital input 2
Start reverse
P)
10 DI3 Digital input 3
Fault reset
P)
A A RS485 signal A FB Communication
Negative
B B RS485 signal B FB Communication
Positive
4 AI2 Analog signal in 2
PID actual value and
Freq. reference
P)
Default:
0(4) - 20 mA, Ri 250
Other:
0 - + 10 V, Ri = 250 k
Selectable through microswitch
5GND
I / O signal ground
13 DO-
Digital Output
Common
Digital Output Common
14 DI4 Digital input 4
Preset speed B0
P)
Positive, Logic1: 18…+30V,
Logic0: 0…5V;
Negative, Logic1: 0…10V,
Logic0: 18…30V;
Ri = 10K (floating)
15 DI5 Digital input 5
Preset speed B1
P)
As DI,
Other: Encoder Input A (fre-
quency up to 10 kHz)
Selectable through microswitch
16 DI6 Digital input 6
External Fault
P)
As DI,
Other: Encoder Input B (fre-
quency up to 10 kHz), Pulse
Train Input (frequency up to 5
kHz)
18 AO Analog Output
Output frequency
P)
0 - 10 V, RL 1 K
0(4) - 20 mA, RL 500
Selectable through microswitch
20 DO Digital signal out
Active = READY
P)
Open collector, max. load 35 V /
50 mA
Table 6.2: Vacon 20 General purpose application default I / O configuration
and connections for control board
P) = Programmable function, see parameter lists and descriptions, chapters
8 and 9.
mA
1-10 k

Table of Contents

Other manuals for Vacon 20