vacon parameters
8
8.15 Fault autoreset parameters (Control panel: Menu PAR -> P14)
NOTE! These parameters are shown, when P17.2 = 0.
8.16 PID control parameters (Control panel: Menu PAR -> P15)
Code Parameter Min Max Unit Default ID Note
Automatic Reset 0 1 0 731
0 = Disabled
1 = Enable
Wait time 0,10 10,00 s 0,50 717 Waiting time after fault
Trial time 0,00 60,00 s 30,00 718 Maximum time for trials
Trials number 1 10 3 759 Maximum trials
Restart Function 0 2 2 719
0 = Ramping
1 = Flying
2 = From Start Function
Table 8.15: Fault autoreset parameters
Code Parameter Min Max Unit Default ID Note
P15.1
Setpoint source
selection
0 Varies 0 332
0 = Fixed setpoint %
1 = AI1
2 = AI2
3 = ProcessDataIn1
(0 -100%)
4 = ProcessDataIn2
(0 -100%)
5 = ProcessDataIn3
(0 -100%)
6 = ProcessDataIn4
(0 -100%)
7 = Pulse train/encoder
8 = AIE1
9 = Temperature input 1
10 = Temperature input 2
11 = Temperature input 3
P15.2 Fixed setpoint 0,0 100,0 % 50,0 167 Fixed setpoint
P15.3 Fixed setpoint 2 0,0 100,0 % 50,0 168
Alternative fixed setpoint,
selectable with DI
Table 8.16: PID control parameters