parameters vacon
91
8
P15.4
Feedback
so
urce selection
0 Varies 1 334
0 = A
I1
1 = AI
2
2 =
ProcessDataIn1
(0 -100%)
3 =
ProcessDataIn2
(0 -100%)
4 =
ProcessDataIn3
(0 -100%)
5 =
ProcessDataIn4
(0 -100%)
6 =
AI2-AI1
7 = P
ulse train / encoder
8 =
AIE1
9 = T
emperature input 1
10 =
Temperature input 2
11 =
Temperature input 3
i
i
i
i
i
i
i
i
i
P15.5
Feedback value
minumum
0,0 50,0 % 0,0 336 Value at minimum signal
P15.6
Feedback value
maximum
10,0 300,0 % 100,0 337 Value at maximum signal
P15.7 P gain 0,0 1000,0 % 100,0 118 Proportional gain
P15.8 I time 0,00 320,00 s 10,00 119 Integrative time
P15.9 D time 0,00 10,00 s 0,00 132 Derivative time
P15.10 Error inversion 0 1 0 340
0 =
Direct (Feedback < Set-
point ->Increase PID out-
put)
1 =
Inverted (Feedback >
Setpoint ->Decrease PID
output)
P15.11
Sleep minimum
frequency
0,00 P3.2 Hz 25,00 1016
Drive goes to sleep mode
wh
en the output frequency
stays below this limit for a
time greater than that
defined by parameter Sleep
delay
P15.12 Sleep delay 0 3600 s 30 1017 Delay for enter sleep
P15.13 Wake up error 0,0 100,0 % 5,0 1018 Threshold for exit sleep
P15.14
Sleep setpoint
boost
0,0 50,0 % 10,0 1071
Referred to setpoint
Code Parameter Min Max Unit Default ID Note
Table 8.16: PID control parameters