8.13 Limit Supervisions (Control panel: Menu PAR -> P12)
Code Parameter Min Max Unit Default ID Note
P12.1
Output freq.
supervision func-
tion
0 2 0 315
0 = Not used
1 = Low limit
2 = High limit
P12.2
Output freq.
supervision limit
0,00 P3.2 Hz 0,00 316
Output frequency super-
vision threshold
P12.3
Torque supervi-
sion function
0 2 0 348
0 = Not used
1 = Low limit
2 = High limit
P12.4
Torque supervi-
sion limit
0,0 300,0 % 0,0 349
Torque supervision
Threshold
P12.5
Unit Temperature
Supervision
0 2 0 354
0 = Not used
1 = Low limit
2 = High limit
P12.6
Unit Temperature
Supervision Limit
-10 100
°C
40 355
Unit temperature super-
vision threshold
P12.7
Analogue input
superv signal
0 Varies 0 356
0 = AI1
1 = AI2
2 = AIE1
P12.8 AI superv ON level 0,00 100,00 % 80,00 357 ON threshold AI superv.
P12.9
AI superv OFF
level
0,00 100,00 % 40,00 358 OFF threshold AI superv.
P12.10
Temperature
supervision input
1 7 1 1431
Binary-coded selection
of signals to use for tem-
perature supervision
B0 = Temperature input 1
B1 = Temperature input 2
B2 = Temperature input 3
NOTE! Hidden until an
option board is con-
nected
P12.11
Temperature
supervision
function
0 2 2 1432
As parameter 12.1, hid-
den until an option board
is connected
P12.12
Temperature
supervision limit
-50,0/
223,2
200,0/
473,2
80,0 1433
Temperature supervision
threshold, hidden until
an option board is con-
nected
Table 8.13: Limit Supervisions