parameters vacon
•
77
8
8.4 Frequency references (Control panel: Menu PAR -> P3)
NOTE! These parameters are shown, when P17.2 = 0.
Code Parameter Min Max Unit Default ID Note
Min frequency 0,00 P3.2 Hz 0,00 101
Minimum allowed
frequency reference
Max frequency P3.1 320,00 Hz
50,00 /
60,00
102
Maximum allowed
frequency reference
P3.3
Remote Control
Place 1 fre-
quency refer-
ence seclection
1 Varies 7 117
1 = Preset speed 0
2 = Keypad
3 = Fieldbus
4 = AI1
5 = AI2
6 = PID
7 = AI1+ AI2
8 = Motor potentiometer
9 = Pulse train / Encoder
10 = AIE1
11 = Temperature input 1
12 = Temperature input 2
13 = Temperature input 3
P3.4 Preset speed 0 P3.1 P3.2 Hz 5,00 180
Preset speed 0 is used as
frequency reference when
P3.3 = 1
P3.5 Preset speed 1 P3.1 P3.2 Hz 10,00 105 Activated by digital inputs
P3.6 Preset speed 2 P3.1 P3.2 Hz 15,00 106 Activated by digital inputs
P3.7 Preset speed 3 P3.1 P3.2 Hz 20,00 126 Activated by digital inputs
P3.8 Preset speed 4 P3.1 P3.2 Hz 25,00 127 Activated by digital inputs
P3.9 Preset speed 5 P3.1 P3.2 Hz 30,00 128 Activated by digital inputs
P3.10 Preset speed 6 P3.1 P3.2 Hz 40,00 129 Activated by digital inputs
P3.11 Preset speed 7 P3.1 P3.2 Hz 50,00 130 Activated by digital inputs
P3.12
Remote Control
Place 2 fre-
quency refer-
ence selection
1 Varies 5 131 As parameter P3.3
P3.13
Motor Poten-
tionmeter Ramp
1 50 Hz/s 5 331 Speed variation rate
P3.14
Motor Poten-
tionmeter Reset
0 2 2 367
0 = No Reset
1 = Reset if stopped
2 = Reset if powered down
Table 8.4: Frequency references