parameter descriptions vacon
131
9
P13.12 STALL TIME
This time can be set between 0.00 and 300.00s.
This is the maximum time allowed for a stall stage. The stall time is counted
b
y an internal up/down counter.
If the stall time counter value goes above this limit the protection will cause a
trip (see P13.5).See Figure 9.20.
Par.13.12
Tr ip a re a
Time
Stall time counter
Stall
No stall
Trip/warning
Par. 13.5
Figure 9.20: Stall time calculation
P13.14 UNDERLOAD PROTECTION: FIELD WEAKENING AREA LOAD
The torque limit can be set between 10.0-150.0 % x T
nMotor
.
This parameter gives the value for the minimum torque allowed when the out-
put frequency is above the field weakening point. If you change parameter P1.4
(Motor nominal current) this parameter is automatically restored to the de-
fault value.
P13.16 UNDERLOAD PROTECTION: TIME LIMIT
This time can be set between 2.0 and 600.0 s.