EasyManua.ls Logo

Vacon 20 - Page 47

Vacon 20
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
installation vacon
41
3
Frame Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI2 0001-0004 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI3 0005 32 2*6+6 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
Table 3.8: Cable and fuse sizes for Vacon 20, 115 V, 1~
Frame Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1 0001-0003 10 2*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI2 0004-0007 20 2*2.5+2.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI3 0009 32 2*6+6 3*1.5+1.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
Table 3.9: Cable and fuse sizes for Vacon 20, 208 - 240 V, 1~
Frame Type
Fuse
[A]
Mains
cable
Cu [mm
2
]
Motor
cable
Cu [mm
2
]
Terminal cable size (min/max)
Main
terminal
[mm
2
]
Earth
terminal
[mm
2
]
Control
terminal
[mm
2
]
Relay
terminal
[mm
2
]
MI1 0001-0003 6 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI2 0004-0007 10 3*1.5+1.5 3*1.5+1.5 1.5-4 1.5-4 0.5-1.5 0.5-1.5
MI3 0011 20 3*2.5+2.5 3*2.5+2.5 1.5-6 1.5-6 0.5-1.5 0.5-1.5
MI4 0012-0025
20
25
40
3*6+6 3*6+6 1-10Cu 1-10 0.5-1.5 0.5-1.5
MI5 0031-0038 40 3*10+10 3*10+10
2.5-50
Cu / Al
2.5-35 0.5-1.5 0.5-1.5
Table 3.10: Cable and fuse sizes for Vacon 20, 208 - 240 V, 3~