parameters vacon
•
75
8
NOTE! These parameters are shown, when P17.2 = 0.
Brake Chopper 0 2 0 504
0 = Disabled
1 = Enabled: Always
2 = Run state
Brake chopper
level
0 911 V varies 1267
Brake chopper control
activation level in volt.
For 240V Supply:
240*1.35*1.18 = 382V
For 400V Supply:
400*1.35*1.18 = 638V
Please note that when
brake chopper is used the
overvoltage controller can
be switched off or the
overvoltage reference level
can be set above the brake
chopper level.
Motor
identification
01 0631
0 = Not active
1 = Standstill identification
(need run command within
20 s to activate)
Rs voltage drop 0,00 100,00 % 0,00 662
Voltage drop over motor
windings as % of U
nmot
at
nominal current.
Overvoltage
controller
02 1607
0 = Disabled
1 = Enabled, Standard
mode
2 = Enabled, Shock load
mode
Undervoltage
controller
01 1608
0 = Disable
1 = Enable
Sine filter 0 1 0 522
0 = Not in use
1 = In use
Modulator type 0 65535 28928 648
Modulator configuration word:
B1 = Discontinuous modu-
lation (DPWMMIN)
B2 = Pulse dropping in
overmodulation
B6 = Under modulation
B8 = Instantaneous DC volt-
age compensation *
B11 = Low noise
B12
= Dead time compensation *
B13
= Flux error compensation *
* Enabled by default
Code Parameter Min Max Unit Default ID Note
Table 8.2: Motor settings