parameters vacon
79
8
P4.13
Accel2 Frequency
Threshold
0.00 P3.2 Hz 0,00 527 0,00 = disabled
P4.14
Decel2 Frequency
Threshold
0,00 P3.2 Hz 0,00 528 0,00 = disabled
P4.15
External Brake:
Open Delay
0,00 320,00 s 0,20 1544
Delay to open brake
after Open frequency
limit is reached
P4.16
External Brake:
Open Frequency
limit
0,00 P3.2 Hz 1,50 1535
Opening frequency from
forward and reverse
direction.
P4.17
External Brake :
Close Frequency
limit
0,00 P3.2 Hz 1,00 1539
Close frequency from
positive direction if no
run command active.
P4.18
External Brake :
Close Frequency
limit in Reverse
0,00 P3.2 Hz 1,50 1540
Close frequency from
negative direction if no
run command active.
P4.19
External Brake :
Open/Close Cur-
rent limit
0,0 200,0 % 20,0 1585
The brake is not opened
if the current does not
exceed this value, and is
closed immediately if
current goes below.
This parameter is set as
a percent of Motor nomi-
nal current.
Code Parameter Min Max Unit Default ID Note
Table 8.5: Ramps and brakes setup
i
i
i
i
i