EasyManuals Logo

Vacon NX series User Manual

Vacon NX series
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #101 background imageLoading...
Page #101 background image
Control Keypad vacon • 99
Local contacts: http://drives.danfoss.com/danfoss-drives/local-contacts/
6
You can return to the previous menu any time by pressing Menu button left.
Figure 63. Selection of language
6.3.8.2
Copy parameters
The parameter copy function is used when the operator wants to copy one or all parameter groups
from one drive to another. All the parameter groups are first uploaded to the keypad, then the
keypad is connected to another drive and then the parameter groups are downloaded to it (or
possibly back to the same drive). For more information, see on Page 100.
Before any parameters can be successfully copied from one drive to another, the Active Front End
has to be stopped when the parameters are downloaded to it:
The parameter copy menu (S6.3) contains four functions:
Parameter sets (S6.3.1)
The user can reload the factory default parameter values and store and load two customised
parameter sets (all parameters included in the application).
On the Parameter sets page (S6.3.1), press Menu button right to enter the edit mode. The text
LoadFactDef begins to blink and you can confirm the loading of factory defaults by pressing the
Enter button. The drive resets automatically.
Alternatively, you can choose any other storing or loading functions with the Browser buttons.
Confirm with the Enter button. Wait until 'OK' appears on the display.
System Menu
S1
S11
READY
I/Oterm
Language
English
READY
I/Oterm
Language
English
READY
I/Oterm
enter
READY
I/Oterm
Francais
Langue
11197.emf

Table of Contents

Other manuals for Vacon NX series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon NX series and is the answer not in the manual?

Vacon NX series Specifications

General IconGeneral
Product typeAC Drive
Output voltage range0-Uin
Frequency range0-500 Hz
Enclosure classesIP00, IP21
Mounting typesWall
Braking chopperIntegrated or external
EMC filterBuilt-in or external
Control modesScalar, Vector
Protection featuresOvercurrent, overvoltage, undervoltage, overtemperature, short circuit
Communication optionsModbus, Profibus, CANopen, Ethernet
Ambient temperature range-10°C to +50°C
Cooling methodAir-cooled

Related product manuals