VAMP 257 Feeder and motor manager
Technical description
VAMP Ltd
96
VAMP 24h support phone : +358 (0)20 753 3264
VM257.EN002
Parameter Value Unit Description
Obj 3 open
status input
DI1; DI2; …
DI32; none
Open information of
object 3
Obj 3 ready
input
DI1; DI2; …
DI32; none
Ready information of
object 3 (spring
charged)
Obj 3 close
command
input
DI1; DI2; …
DI32; none
Close command digital
input for object 3
Obj 3 open
command
input
DI1; DI2; …
DI32; none
Open command digital
input for object 3
Obj 3 pulse 0.02 … 600.00 s
Pulse length of open
and close commands
for object 3
Obj 3 ready
timeout
0.02 … 600.00 s
Timeout of ready
indication for object 3
Control Obj 3 Open;
Close
Control object 3
Obj 4 close
status input
DI1; DI2; …
DI32; none
Close information of
object 4
Obj 4 open
status input
DI1; DI2; …
DI32; none
Open information of
object 4
Obj 4 ready
input
DI1; DI2; …
DI32; none
Ready information of
object 4 (spring
charged)
Obj 4 close
command
input
DI1; DI2; …
DI32; none
Close command digital
input for object 4
Obj 4 open
command
input
DI1; DI2; …
DI32; none
Open command digital
input for object 4
Obj 4 pulse 0.02 … 600.00 s
Pulse length of open
and close commands
for object 4
Obj 4 ready
timeout
0.02 … 600.00 s
Timeout of ready
indication for object 4
Control Obj 4 Open;
Close
Control object 4
Obj 5 close
status input
DI1; DI2; …
DI32; none
Close information of
object 5
Obj 5 open
status input
DI1; DI2; …
DI32; none
Open information of
object 5
Obj 5 ready
input
DI1; DI2; …
DI32; none
Ready information of
object 5 (spring
charged)
Obj 5 close
command
input
DI1; DI2; …
DI32; none
Close command digital
input for object 5
Settings
Obj 5 open
command
input
DI1; DI2; …
DI32; none
Open command digital
input for object 5

Table of Contents