VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
27
Operation time modes
Setting
Curve family
Delay type
Parameters A…E
Definite delay
Inverse time
coefficient
Programmable curve
1 … 3
VAMPSET
X X X
X
X X
Local panel
X X X
X
X
Setting availability
Requires restarting
X
1
Standard
characteristics
IEC…RI NI…RXIDG
X
2
Formula
parameters
IEC…IEEE2 Parameters X
X
3
16 programmable
[current, time]
points
Prg1..Prg3
X
Operation time mode
Definite time (DT)
DT DT X
Relay will show the currently used inverse delay curve on the
local panel display.
Programmable inverse time curves
(only for I
dir
> and I
dir
>>):
The [current, time] curve points are programmed using
VAMPSET. There are some rules for defining the curve points:
• configuration must begin from the top most line
• line order must be as follows: the smallest current (longest
operation time) on the top and the largest current (shortest
operation time) on the bottom
• all unused lines (on the bottom) should be filled with ‘1.00
0.00s’