VAMP Ltd Feeder and motor manager
Technical description
VAMP 257
VM257.EN002 VAMP 24h support phone : +358 (0)20 753 3264
27
Operation time modes
Setting
Curve family
Delay type
Parameters A…E
Definite delay
Inverse time
coefficient
Programmable curve
1 … 3
VAMPSET
X X X
X
X X
Local panel
X X X
X
X
Setting availability
Requires restarting
X
1
Standard
characteristics
IEC…RI NI…RXIDG
X
2
Formula
parameters
IEC…IEEE2 Parameters X
X
3
16 programmable
[current, time]
points
Prg1..Prg3
X
Operation time mode
Definite time (DT)
DT DT X
Relay will show the currently used inverse delay curve on the
local panel display.
Programmable inverse time curves
(only for I
dir
> and I
dir
>>):
The [current, time] curve points are programmed using
VAMPSET. There are some rules for defining the curve points:
configuration must begin from the top most line
line order must be as follows: the smallest current (longest
operation time) on the top and the largest current (shortest
operation time) on the bottom
all unused lines (on the bottom) should be filled with ‘1.00
0.00s’