INSTALLATION  Series 
 
42/129
Edition 2019-05-03  963283EA
 
4.6  Valve configuration 
 
Basic valve configuration must be adapted according to application needs. 
Definition of valve plate position in case of: 
 
•  After power up, default is ‘close‘. 
•  Power failure, default is ‘not defined‘. Only for versions that have Power Fail Option equipped [653 . . 
- . . C . - . . . . or 653 . . - . . H . - . . . . ]. 
•  Network failure, for default settings refer to individual product data sheet. 
 
Local operation: 
(‘Control View’, ‘Control Performance Analyzer’)
Remote operation: 
(Refer to chapter «Setup commands» for details) 
With CPA: 
•  Do valve configuration in menu ‘Valve 
/ Setup’. 
1.  Send VALVE CONFIGURATION 
 
 
4.6.1  Homing Start Option 
Homing start option defines when the valve performs the homing procedure.  
Parameter  Description 
Homing start option defines when the valve performs the homing 
procedure. 
 
Standard  Do homing after restart if valve is not in 
Open Command  Do homing on an open command 
Move Command  Do homing on any move command 
At Startup  Do homing after restart 
Homing Command  Do homing on homing command 
Move 
Command/Standard 
Settings from move commands, without 
homing in close position by close command 
This control mode is set after a successful homing. 
In case the “End Control Mode” is set to “Position”, this parameter 
defines which position is set after successful homing. 
 
Parameter location: 
CPA  RS232 
Valve->Homing  Refer to RS232-setup command for detail 
 
 
4.6.2  Power Failure Option 
These settings define what the valve is doing in case the power fails. 
Parameter  Description 
‘True’ enables the power fail reaction, in case of ‘False’ there is no 
reaction on a power fail 
Current power fail state 
Defines the functionality in case of power fails. This can be “open” or