Series 65  INSTALLATION 
 
963283EA  Edition 2019-05-03  69/
 
4.11.3  Inquiry commands 
Inquiry function 
Command  Acknowledgement 
Description 
POSITION 
Get 
A:  A:aaaaaa 
data length  6 characters 
aaaaaa  position, return value depends on configuration, 
    refer to «Setup commands, COMMUNICATION RANGE» 
    for details 
This function returns the current valve position. 
Remark: 999’999 is returned when the position is unknown, for example after power up 
during synchronization 
PRESSURE 
Get 
P:  P:saaaaaaa 
data length  8 characters 
s   sign, 0 for positive readings, - for negative readings 
aaaaaaa  pressure, return value depends on configuration, 
    refer to «Setup commands, COMMUNICATION RANGE» 
    for details 
 
This function returns the actual pressure. 
SENSOR 1 OFFSET 
Get 
i:60  i:60aaaaaaaa 
data length  8 characters 
aaaaaaaa  sensor 1 offset (-140000 ...  0140000   =   -1.4V ... +1.4V) 
 
This function returns the sensor 1 offset voltage (adjusted by ZERO). 
SENSOR 2 OFFSET 
Get 
i:61  i:61aaaaaaaa 
data length:  8 characters 
aaaaaaaa  sensor 2 offset (-140000 ...  0140000   =   -1.4V ... +1.4V) 
 
This function returns the sensor 2 offset voltage (adjusted by ZERO). 
SENSOR 1 READING 
Get 
i:64  i:64saaaaaaa 
data length  8 characters 
s   sign, 0 for positive readings, - for negative readings 
aaaaaaa  sensor 1 reading, return value depends on configuration, 
    refer to «Setup commands, COMMUNICATION RANGE» 
    for details 
This function returns direct reading from sensor 1 input. 
SENSOR 2 READING 
Get 
i:65  i:65saaaaaaa 
data length  8 characters 
s   sign, 0 for positive readings, - for negative readings 
aaaaaaa  sensor 2 reading, return value depends on configuration, 
    refer to «Setup commands, COMMUNICATION RANGE» 
    for details 
This function returns direct reading from sensor 2 input.