INSTALLATION  Series 
 
78/129
Edition 2019-05-03  963283EA
 
Setup function 
Command  Acknowledgement 
Description 
SENSOR 2 
LINEARIZATION 
Set 
s:18aaaabbbb 
s:18 
Get 
i:18  i:18aaaabbbb 
data length   8 characters 
 
a  logarithmic resolution[ millivolt /decade] 
  0000 = linearizing off 
  0001 = min. value 
  9999 = max. value 
  (default value: 0000 = linearizing off) 
 
b  full scale [millivolt] 
  0001 = min. value 
  9999 = max. value 
  (default value in logarithmic mode: 5324 = 5.324V) 
  (becomes linear full scale = 1000000) 
 
Pressure control algorithm adaptive downstream needs a linear sensor signal, therefore a 
logarithmic signal must be linearized. 
 
Example: s:1700000000 = Linear sensor 
Example: s:1810007800 = Logarithmic sensor (1.0V/decade, Linear full scale at 7.8V)
 
SENSOR AVERAGE 
Set 
s:19abbbbbbb  s:19 
Get 
i:19  i:19abbbbbbb 
data length   8 characters 
 
a 
Average time 
 = 0.0 sec 
1 = 0.1 sec 
2 = 0.2 sec 
3 = 0.3 sec 
4 = 0.4 sec 
5 = 0.5 sec 
6 = 0.6 sec 
7 = 0.7 sec 
8 = 0.8 sec 
9 = 0.9 sec 
A = 1.0 sec 
b 
Reserved  set to 0000000 
 
Remark: For pressure control averaging of sensor signal is not recommended. 
This function does the sensor average configuration.