Series 65  INSTALLATION 
 
963283EA  Edition 2019-05-03  87/
 
Example:  
Set RAMP MODE of the Fixed 1 pressure controller to the value 0 (fixed time) 
Command  Pressure 
controller 
Parameter selection variable  Parameter value 
s:02 
B (a)  02 (bb)  0 (c) 
 
 s:02B020 
 
 
 
To optimize Fixed 1 control algorithm, refer to chapter «Tuning of control 
performance». 
 
 
 
4.11.5.3  Fixed 2 control algorithm 
Parameter  Command  Request  Data Type  Values 
RAMP TIME 
Pressure 
setpoint ramp 
time [s] 
Set 
s:02C01c 
s:02 
FLOAT 
c = 0.00…1
’
000
’
000.0 
Default is: 0.00 
Get  i:02C01 
i:02C01c 
RAMP MODE 
Set 
s:02C02c 
s:02 
UINT 
c = 0 or 1 
0 = constant time 
1 = constant slope 
Default is: 0 
Get  i:02C02 
i:02C02c 
CONTROL 
DIRECTION 
Set 
s:02C03c 
s:02 
UINT 
c = 0 or 1 
0 = downstream 
1 = upstream 
Default is: 0 
Get  i:02C03 
i:02C03c 
P-GAIN 
Set 
s:02C04c 
s:02 
FLOAT 
c = 0.001…100 
Default is: 0.1 
Get  i:02C04 
i:02C04c 
I-GAIN 
Set 
s:02C05c 
s:02 
FLOAT 
c = 0…100.0 
Default is: 0.1 
Get  i:02C05 
i:02C05c 
 
Explanation: Refer to: «Fixed 1 control algorithm»