Vertiv | Liebert® CRV4 | User Manual 8
Installation
2.3. Environmental Requirements
2.3.1. Operating Environment
The operating environment requirements for Liebert® CRV4 are given in Table 2-2.
Table 2-2 Operating Environment Requirements
Item Requirement
Ambient temperature
Indoor
18 °C to 40 °C, 20% to 60% RH
Outdoor
-20 °C to +45 °C, if a low temperature kit is congured, the
lowest outdoor operation temperature is -34 °C.
Protection level
(outdoor unit)
IP20
Altitude <1000 m, Derating is required when located altitude is above 1000 m.
Operation voltage
range
380 V to 415 V±10%, 3 Ph+N ~50Hz / 60Hz
2.3.2. Storage Environment
The storage environment requirements for Liebert CRV4 are given in Table 2-3.
Table 2-3 Storage Environment Requirements
Item Requirement
Storage
environment
Indoor, clean, no dust
Ambient
humidity
< 95% RH
Ambient
temperature
-40 °C to +70 °C
Storage time
Total transportation and storage time should not exceed six months, otherwise
the performance of the system needs to be re-calibrated.
Please contact Vertiv representative when operating in the following conditions
The voltage of the air conditioning unit is beyond the range of the operating voltage.
The altitude is higher than 1000 m.
If the application condition is other than Table 2-2.