EasyManua.ls Logo

Vertiv Liebert CR045 - System Installation Mode

Vertiv Liebert CR045
126 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Vertiv | Liebert® CRV4 | User Manual 14
Mechanical Installation
The following points should be considered before checking out the overall layout diagram
: Factory piping
: Field piping (by technical personnel)
Components (marked with *) are not supplied by Vertiv and are recommended for proper circuit operation
& maintenance.
Additional components (marked with +) are required when the equivalent length exceeds 30 m.
3.1.2. System Installation Mode
The installation modes of the Liebert® CRV4 series unit are shown in Figure 3-2 and Figure 3-3.
No. Description No. Description
1 Outdoor unit 7 Heat insulation oor
2 Back bend
(must be higher than the highest copper pipe of the condenser) 8 Floor
3 Liquid line
(avoid exposure to direct sunlight) 9 Condensed water out
4 Trap 10 Humidier water in
5 Slope discharge 11 Raised oor
6 Sealed 12 Indoor unit
Figure 3-2 The Outdoor Unit is Placed Higher than the Compressors during Installation

Table of Contents

Related product manuals