Mechanical Installation
3.4.2. Adding Lubricant Oil
The charging refrigerant can dilute the lubricant oil in the system and aects the lubricating & cooling
properties of the lubricant oil. Therefore, the lubricant oil should be added in the beginning. The lubricant oil
used in the Liebert® CRV4 air conditioner is given in Table 3-9.
Table 3-9 Types of Lubricant Oil
Unit Model Types of Lubricant Oil
CR025 POE (32-3MAF)
CR035 PVE (FVC68D)
CR045 POE (32-3MAF)
Table 3-10 provides the amount of lubricant oil to be added.
Table 3-10 Adding Lubricant Oil
Liquid Pipe OD
(mm)
CR025, CR035, CR045
30 m >30 m
12.7
Lubricant oil charging is
not needed
Amount of lubricant oil (ml) to
be added = More than 30 m
part even pipe added amount of
refrigerant × 10%
16
19
22
25
Consult Vertiv representative for more details on adding the lubricant oil.
CR025 and CR045 units use POE type (32-3MAF) lubricant oil, and CR035 units use PVE type (FVC68D)
lubricant oil
Do not use inferior quality refrigerant.
For any consequences resulting from inferior quality refrigerant, Vertiv does not assume warranty
responsibility.
Select the type of lubricant oil in accordance with the compressor manufacturer’s specication.