Vertiv | Liebert CRV+ | User Manual 58
Listing 3.5
Settings
Alarm history record
Alarm status record
Audible alarm
Alarm prompt
ENA Yes Yes Yes Yes
DISA Yes Yes No No
OFF No No No No
The following alarms are crucial fault alarms and hence, cannot be set to OFF. However, they
can be set to ENA and DISA.
Air Lost
Hi Exh Temp
Hi Exh Lock
Lo Exh SH
Lo Exh Lock
HP Abnor
HP Alm
HP Lock
LP Alm
LP Lock
LP Sen Lock
Water Alm
Water UF
Fan Alm
Heat Alarm
Remote Alm
Sensor Alarm
Select the Sensor Alarm item on the Alarm Set screen to access the menu. Press the Up and Down button
to scroll through the menu items in the Sensor Alarm menu.
Figure 3-13 depicts the Sensor Alarm menu items.
Figure 3-13 Sensor Alarm