NOTE: A separate neutral wire does not need to be run to the Liebert® Drycooler.
No. of Fans Model No. Voltage Phase FLA WSA OPD
Standard Models
1 33, 69, 092, 109, 112
208/230
1 4.8 6 15
3 3.5 4.4 15
460 3 1.7 2.1 15
575 3 1.4 1.8 15
2 139, 174, 197, 225
208/230 3 7.0 7.9 15
460 3 3.4 3.8 15
575 3 2.8 3.2 15
3 260, 310, 350
208/230 3 10.5 11.4 15
460 3 5.1 5.5 15
575 3 4.2 4.6 15
4 352, 419, 466, 491
208/230 3 14.0 14.9 20
460 3 6.8 7.2 15
575 3 5.6 6.0 15
6 620, 650, 700
208/230 3 21.0 21.9 25
460 3 10.2 10.6 15
575 3 8.4 8.8 15
8 790, 880, 940
208/230 3 28.0 28.9 35
460 3 13.6 14.0 20
575 3 11.2 11.6 15
Liebert® Quiet-Line Models
1 40, 57, 60
208/230 3 1.8 2.3 15
460 3 0.9 1.1 15
575 3 0.7 0.9 15
2 80, 111, 121
208/230 3 3.6 4.1 15
460 3 1.8 2.0 15
575 3 1.4 1.6 15
3 158, 173, 178
208/230 3 5.4 5.9 15
460 3 2.7 2.9 15
575 3 2.1 2.3 15
4 205, 248
208/230 3 7.2 7.7 15
460 3 3.6 3.8 15
575 3 2.8 3.0 15
Table 6.2 60Hz Electrical Values—Drycoolers without Pump Controls
6 Electrical Connections
41