No. of Fans Model No. Voltage Phase FLA WSA OPD
6 347, 356
208/230 3 10.8 11.3 15
460 3 5.4 5.6 15
575 3 4.2 4.4 15
8 453, 498
208/230 3 14.4 14.9 20
460 3 7.2 7.4 15
575 3 5.6 5.8 15
Values are calculated per UL 1995. OPD values may be adjusted higher than calculations to compensate for maximum
anticipated application temperatures.
Table 6.2 60Hz Electrical Values—Drycoolers without Pump Controls (continued)
No. of Fans Model # Voltage Phase FLA
Standard Models
1
33, 69, 92,
109, 112
200/230 1 4.0
380/415 3 1.7
2
139, 174, 197,
225
380/415 3 3.4
3
260, 310,
350
380/415 3 5.1
4
352, 419,
466, 491
380/415 3 6.8
6
620, 650,
700
380/415 3 10.2
8
790, 880,
940
380/415 3 13.6
Quiet-Line Models
1 40, 57, 60 380/415 3 0.9
2 80, 111, 121 380/415 3 1.8
3 158, 173, 178 380/415 3 2.7
4 205, 248 380/415 3 3.6
6 347, 356 380/415 3 5.4
8 453, 498 380/415 3 7.2
Table 6.3 50Hz Electrical Values—Drycoolerswithout
Pump Controls
Vertiv | Liebert® Drycooler Installer/User Guide