No. of Fans: 6 8
Model #: 620, 650, 700 790, 880, 940
Pump hp Ph
F
L
A
W
S
A
O
P
D
F
L
A
W
S
A
O
P
D
208/230/60
0.75 1 — — — — — —
0.75 3 24.5 25.4 30 31.5 32.4 40
1.5 3 27.6 29.3 35 34.6 36.3 40
2.0 3 28.5 30.4 35 35.5 37.4 45
3.0 3 31.6 34.3 40 38.6 41.3 50
5.0 3 37.7 41.9 50 44.7 48.9 60
7.5 * 3 45.2 51.3 70 52.2 58.3 80
460/60
0.75 3 11.8 12.2 15 15.2 15.6 20
1.5 3 13.2 14.0 20 16.6 17.4 20
2.0 3 13.6 14.5 20 17.0 17.9 20
3.0 3 15.0 16.2 20 18.4 19.6 25
5.0 3 17.8 19.7 25 21.2 23.1 30
7.5 3 21.2 24.0 30 24.6 27.4 35
575/60
0.75 3 9.7 10.1 15 12.5 12.9 15
1.5 3 10.8 11.4 15 13.6 14.2 20
2.0 3 11.1 11.8 15 13.9 14.6 20
3.0 3 12.3 13.3 15 15.1 16.1 20
5.0 3 14.5 16.0 20 17.3 18.8 20
7.5 3 17.4 19.7 25 20.2 22.5 30
Values are calculated per UL 1995. Pump FLA values used are based on NEC tables for motor horsepower. OPD values may be adjusted higher than calculations to compensate for
maximum anticipated application temperatures.
* May require electrical component(s) with higher capacity in the drycooler. Consult factory representatives for assistance before ordering.
Table 6.5 60Hz Electrical Values—Standard Drycoolers with Integral Pump Controls, 6–8Fans