50-250kVA, 480V, 60Hz User Manual | 10
2.2 Preliminary Checks
2.2.1 Identification
The equipment supplied has an identification tag on the back of the main door listing the type
and size of the UPS.
2.3 UPS Location
2.3.1 Positioning the UPS
Choose a location for the UPS that offers:
Easy connection to inputs, outputs and auxiliary equipment
Enough space to service the UPS
Air circulation sufficient to expel heat produced by UPS
Protection against moisture and excessive humidity
Protection against dust and other particulate matter
Compliance with fire prevention regulations and practices
Operating environment temperature of 74-80°F (23-27°C) for maximum battery life
2.3.2 Environmental Considerations
Before installing the Liebert
®
EXM
, verify that the UPS room satisfies the environmental
conditions stipulated in 7.2 - UPS Environmental Requirements, paying particular attention to
the ambient temperature and air exchange system.
The UPS unit should be installed in a cool, dry, clean-air environment with adequate ventilation to
keep the ambient temperature within the specified operating range 32°F to 104°F (0°C to 40°C).
For optimal UPS system performance and service life, maintain the operating temperature within
the range of 74-80°F, (23-27°C).
The Liebert
®
EXM
is cooled by internal fans. Cooling air enters the unit through the front of the
unit and is exhausted out the top. To permit proper air flow and prevent overheating, do NOT
block or cover the ventilation openings or blow air down onto the unit. The UPS requires 24 in.
(610mm) ventilation clearance above the unit.
See Table 26 for details on heat dissipation.