Vertiv | Liebert® EXM
50-250kVA, 480V, 60Hz User Manual | 73
7.0 SPECIFICATIONS AND TECHNICAL DATA
7.1 Conformity and Standards
The Liebert
®
EXM
has been designed to conform to the following standards:
The Liebert
®
EXM
has UL and c-UL approval.
7.2 UPS Environmental Requirements
The Liebert
®
EXM
is designed to operate under the following environmental conditions without
damage or degradation in electrical operating characteristics:
Safety
UL 1778, 5th Edition, CSA 22.2
107.3-14
Surge IEC 61000-4-5 Criteria B
Harmonics IEC 61000-3-4
Electrical Fast
Transient
IEC 61000-4-4, Criteria B
ESD IEC 61000-4-2, Criteria B
FCC Part 15, Class A
Radiated Immunity IEC 61000-4-3, Criteria A
Conducted
Immunity
IEC 61000-4-6, Criteria A
Low-Frequency
Signals
IEC 61000-2-2 Criteria A
Transportation ISTA Procedure 1H
ISO 9001
Misc OSHA, ASME, NEMA PE-1
Table 13 Environmental requirements
Item Requirements
Acoustical Noise, dBA, at 55 in.
(1.4m)
<69
Operating Altitude
3200ft. (1000m). (1% maximum kW derate per 300ft.
[100m] rise between 3200 and 9800ft. [1000-3000m])
Relative Humidity 0 to 95% Non-Condensing
Operating Temperature 32-104°F (0-40°C) No Derating
UPS Storage/Transport
Temperature
-4 to 158°F (-20 to 70°C)
Table 14 UPS mechanical characteristics
Rated Power, kVA
50 - 200 250
Dimensions
W x D x H, in (mm)
23-5/8 x 39-3/8 x 78-3/4
(600 x 1000 x 2000)
33 x 39-3/8 x 78-3/4
(840 x 1000 x 2000)
Color RAL 7021 (Black) RAL 7021 (Black)
Protection Degree IEC (60529) IP20 IP20