Enclosure G - Ultrasonic Humidier
G - 3 Liebert
®
PDX, EconoPhase Version - UM - 265133 - 29.08.2019
G. 3 - Start - up and operation
G. 3.1 - Start - up
Before using the humidier, check the following:
Supply and drain connections.
That the cut- o󰀨 tap is open.
All wiring.
Earthing.
To start the humidier simply switch on the air conditioner, which will, in turn, automatically start and stop the humidier as required.
The (adjustable) parameters which determine humidier operation have already been factory-preset (see iCOM manual).
Refer to iCOM manual and HSU08RM000 manual for details.
G. 3.2 - Operation
Ultrasonic humidier operates on the principle of ultrasonic nebulization.
The mist generated in the water tank by means of the transducer is blown into the room by the built-in fan. The humidier consists of
nebulization modules, solenoid valve for the control of the supply water, oat switch and a case that houses the fan.
Refer to HSU08RM000 manual for details.
G. 4 - Maintenance
If the humidier is not used for a long period, the water must be drained o󰀨.
NEVER operate the humidier without air supply.
Before performing any operations, check that the humidier is disconnected from the power supply; carefully read and follow the
instructions contained in the manual.
G. 4.1 - Periodical checks
1. Check drain lines and trap for clogs
2. Check/clean pan for dust
3. Check wire connections (inside humidier box)
4. Check status of humidier air lters