LaserCOMPACT Product Guide VESDA
®
28
1.11 Preliminary Systems Check
A preliminary systems check is required after installing the LaserCOMPACT detector, before it is
commissioned for use. The check can be conducted by connecting the detector to a LCD
Programmer or using VSC, or VSM4 PC based software. The preliminary systems check
includes:
Conducting a VESDAnet communications check
Accepting factory default configurations, or changing to site requirements
Normalizing the air flow
Conducting a basic pass/fail smoke test
For details on preliminary systems check refer to the LCD Programmer or the relevant software
manuals. Refer to the VESDA LCD Programmer and Commissioning Guides for further details.
1.12 Maintaining and Servicing the Detector
To maintain the LaserCOMPACT detector at its peak performance the maintenance schedule
given below should be followed. Maintenance can be conducted by the original installer, a
VESDA distributor, or a service contractor. To work effectively the LaserCOMPACT detector
needs to be supported by a well designed pipe network. The VESDA Maintenance Manual
contains a schedule for pipe network maintenance.More frequent maintenance may be
necessary for harsh environments or be required by your local fire authority.
Table 8 - Maintenance schedule for LaserCOMPACT detector
Caution: When a VESDA detector has been isolated, no fire warnings will be issued by the
VESDA LaserCOMPACT and any fire will go undetected. Prior to any maintenance
or testing:
Note: Inform appropriate supervising authority about the risk associated with isolating a
VESDA address (formerly known as a VESDA Zone).
Note: Ensure that any ancillary devices dependent on the VESDA LaserCOMPACT is/are
isolated before work is begun.
Maintenance Check Quarterly
Six
Monthly
Annual
Every Two
Years
Power Supply X
Check Pipe Network X
Filter Inspection X
Pipe Integrity Smoke Test X
Check Pipe Flow X
Clean Sampling Point. X
Flush Pipe Network X