LaserCOMPACT Product Guide VESDA
®
14
Default Settings
Table 3 - Default values for the LaserCOMPACT detector
Parameter Default Value
Range Minimum
Access
Level
Minimum Maximum
Event Log - Events
• Smoke Level Enabled N/A N/A Adm
• Alarms Enabled N/A N/A Adm
• Faults Enabled N/A N/A Adm
• User Action Enabled N/A N/A Adm
Fire Threshold 0.2% obs/m
(0.062% obs/ft.)
0.015% obs/m
(0.0046% obs/ft.)
20% obs/m
(6.25% obs/ft.)
Adm
Pre-Alarm Threshold 0.14% obs/m
(0.044% obs/ft.)
0.010% obs/m
(0.0031 obs/ft.)
1.995% obs/m
(0.6234% obs/ft.)
Adm
Alert Threshold 0.08% obs/m
(0.025% obs/ft.)
0.005% obs/m
(0.0015 obs/ft.)
1.990% obs/m
(0.6218% obs/ft.)
Adm
Alarm Delays…Fire 10 seconds 0 seconds 60 seconds Adm
Alarm Delays…Pre-Alarm 10 seconds 0 seconds 60 seconds Adm
Alarm Delays…Alert 10 seconds 0 seconds 60 seconds Adm
Delay Times Simultaneous Simultaneous Cumulative Adm
Instantaneous - Fire Disabled N/A N/A Adm
AutoLearn 14 days
0 Hours
0 Minutes
0 Days
0 Hours
15 minutes
15 days
23 Hours
59 Minutes
Adm
Adm
Adm
Air flow Thresholds:
• High Urgent
• High Minor
• Low Minor
• Low Urgent
130%
120%
80%
70%
105%
105%
25%
25%
200%
200%
95%
95%
Adm
Adm
Adm
Adm
Communications:
• Open-ended loop
• Preferred Port
• Network Delay
• Health Check
None
A
15 seconds
45 seconds
N/A
N/A
10 seconds
40 seconds
N/A
N/A
45 seconds
60 seconds
Adm
Dst
Dst
Dst
Device ID Name/Location N/A N/A Adm
Faults Latched Latched N/A N/A Adm
Filter Service Interval 1825 days (5
years)
1 day
(Dependent up
on environment)
1825 days
(5 years)
Adm